Technical Selection - Circular Damper GD-C
2.1.1. Gastight Circular Damper GD-C
The gastight circular shut-off damper GD-C in solid and maintenancefree design, is used for systems with high tightness requirements.
Data
Dimensions | DN 150, DN 200, DN 250, DN 360, DN 400 |
Actuator | electrical, pneumatic, manual, or emergency actuating by means of Hand wheel |
Admissible design temperature | up to +100 °C |
Admissible operating pressure | 10 000 Pa |
Adm. leakage rate damper blade incl. seat of damper clade acc. DIN 25 496 | < 10 l/(h ⋅ m²) at 1 bar, 20 °C and Δp = 2 000 Pa |
Adm. leakage rate housing incl. shaft transition acc. DIN 25 496 | < 10 l/(h ⋅ m²) at 1 bar, 20 °C and Δp = 2 000 Pa |
Material Robust damper housing Circular damper blade Gas-tight shaft transition through housing |
stainless steel, material 1.4301 (AISI/SAE 304), in gastight design stainless steel, material 1.4301 (AISI/SAE 304) shaft sealing made of viton |
Features
- The actual leakage rates for housings and seat of damper blade are much lower than specified in the requirement according to DIN 25 496
- The damper is designed to operate without any failure at an operating pressure of 1.1- times of the admissible operating pressure of the damper
- The tightness of seat of damper blade is testable in built-in situation
- For maintenance purposes, e. g. lubricating, if required, there is no dismantling of the damper from the duct system necessary
- All media touched parts are welded continuously and without gaps to ensure an easy decontamination