4.5. Wall displacement outlet Q-WL, Q-WR and Q-WK

Installation in upper section of room wall (ideally corridor wall) below ceiling.

Data

Type Q-WL Linear wall displacement outlet
Volume flow rate range up to 28 l/(s•m) [100 m³/(h•m)]
Discharge velocity ≤ 0.19 m/s
Sound power level ≤ 33 dB(A) ref. 10-12 W
Height 180 mm
Standard length 0.6, 0.8, 1.0 and 1.2 m
Type Q-WR Circular wall displacement outlet
Volume flow rate range up to 36 l/s [130 m³/h]
Discharge velocity ≤1 m/s
Sound power level ≤ 34 dB(A) ref. 10-12 W
Nominal diameter DN 80, DN 100 and DN 125
Outside diameter 190, 220 and 260 mm
Type Q-WK Combined wall displacement outlet
Volume flow rate range up to 28 l/(s•m) [100 m³/(h•m)]
Discharge velocity ≤ 0.19 m/s
Sound power level ≤ 32 dB(A) ref. 10-12 W
Standard length 0.6; 0.8 und 1.0 m
Height 280 mm
Standard length 1.2 m 
Height 310 mm

Features

  • Installation height 2 to 4 m
  • Jet pattern downwards along the wall, then over the floor and finally vertical upflow through the occupied zone to the ceiling zone
  • Minimum supply air temperature 16 °C
  • Minimum distance to ceiling 120 mm
  • Connection from behind
  • Type Q-WL - Rectangular outlet
  • Type Q-WR - Circular outlet
  • Type Q-WK - Combined outlet with supply air and return air segment