Technical Selection IG-M-LB (in German only)
5.2.3. Induction unit for mixing ventilation IG-M-LB, for horizontal floor mounting
Induction unit for cooling, heating, and fresh air supply along the building facade, via a raised floor, providing a high level of thermal comfort.
Data
Primary air volume flow rate | 4 – 36 l/s [15 – 130 m³/h] |
Cooling capacity (total) | max. 1 320 W |
Cold water temperature | 15 / 17 °C |
Heating capacity | max. 1 200 W |
Hot water temperature | 50 / 40 °C |
Heating capacity with self-convection | 350 W |
Nominal unit width | 1 200 mm (available 800, 900, 1 200, 1 350, 1 600 mm) |
Grille depth | 380 or 500 mm |
Height | 220 mm |
Features:
- Low pressure loss (70 to 200 Pa), therefore energy-saving operation
- Low sound power level
- Heating also possible without primary air, which saves energy when heating at night and at weekends
- Heat exchanger cleanable from the top or the bottom (in compliance with requirements of VDI 6022). The large fin spacing enables easy cleaning and obviates the need for a filter.
- Suitable for new or refurbished buildings