5.2.3. Induction unit for mixing ventilation IG-M-LB, for horizontal floor mounting

Induction unit for cooling, heating, and fresh air supply along the building facade, via a raised floor, providing a high level of thermal comfort.

Data

Primary air volume flow rate 4 – 36 l/s [15 – 130 m³/h]
Cooling capacity (total) max. 1 320 W
Cold water temperature 15 / 17 °C
Heating capacity max. 1 200 W
Hot water temperature 50 / 40 °C
Heating capacity with self-convection 350 W
Nominal unit width 1 200 mm (available 800, 900, 1 200, 1 350, 1 600 mm)
Grille depth 380 or 500 mm
Height 220 mm

Features:

  • Low pressure loss (70 to 200 Pa), therefore energy-saving operation
  • Low sound power level
  • Heating also possible without primary air, which saves energy when heating at night and at weekends
  • Heat exchanger cleanable from the top or the bottom (in compliance with requirements of VDI 6022). The large fin spacing enables easy cleaning and obviates the need for a filter.
  • Suitable for new or refurbished buildings
>