5.2.4. Rectangular floor displacement outlet Q-BR

The rectangular floor displacement outlet ist designed to deliver supply air to commercial rooms with raised floors or floor plenums.

Data

Supply air volume flow rate up to 55 l/(s·m) [200 m³/(h·m)]
Temperature difference
supply air to indoor air
–1 to –6 K
Unit length 800, 1 000, 1 200 (standard), 1 450, 1 700, 1 900 mm
Unit depth 140, 180, 260 (standard), 340 mm
Unit height 190 mm (standard)
130 mm (supply air connection at the bottom)

 

Features

  • Combined mixing/displacement flow or hybrid flow as described in German VDI 3804 Guideline
  • For mounting in raised Floors
  • Volume flow rate up to 55 l/(s·m) [200 m³/(h·m)], one-way or two-way discharge
  • Draught-free indoor air flow with very low air velocities in the occupied Zone
  • Large supply air coverage (up to 6 m)