5.3.2. Semi-trapezoidal displacement outlet VA-TH

For factories with airborne dust, aerosols or fibres and permanent cooling.

Data

Volume flow rate range 70 – 415 l/(s•m) [250 – 1 500 m³/(h•m)]
Width 250 and 500 mm
Length 1 200, 1 500 and 1 800 mm
Coverage zone of supply air jets 2 – 3 m

Features

  • Low-turbulence displacement flow
  • Installation along a wall or row of pillars; supply air intake through connection spigot positioned at the top or at the back, rectangular or circular
  • For applications with permanent cooling
  • Discharge direction from horizontal flow to vertical downflow
  • Discharge height 3 to 4 m